Applications include
commercial and residential interior surfaces such as paneling, non-porous
substrates, veneer, gypsum board, wood, plastic, previously treated
surfaces and MDF. |
|
Advantages:
Class A one coat system. FLAME SPREAD 10. Class A, FLAME SPREAD 0 for 30
minute NFPA 703 with two coats. Flame Stop, Intumescent Paint is user
friendly, water based, non-toxic labor saving, mold inhibitor, fast
curing, high coverage rate, stain blocker, may be used as a primer or
finish coat.
Limitations:
Do not dilute. Storage Range: 45 degrees F. to 110 degrees F. Shelf
life: 1 year if kept within storage temperatures. We suggest a small
compatibility test.
Applicable Standards:
Flame Stop IM was tested to the following standards:
ASTM E-84, NFPA 255, UL 723: Omega Point Laboratories # 8746-108578
ASTM E-84, NFPA 255, NFPA 703 30 minute : SWRI (Southwest Research
Institute) #01.10932.01.195
|
|
Application:
Flame Stop IM should be applied as is by spray, brush or roll. Use
airless sprayer suitable for applying latex-based paint. Tips sizes vary
however we suggest a .017. Apply at the rate of 150 square feet per
gallon for ASTM E-84. For NFPA 703 (30 minute test) apply two coats at
200 square feet per gallon.
*****After treatment a 24 hour conditioning
period is necessary before testing*****
FLAME SPREAD 10 AND SMOKE DEVELOPED 45;
NFPA 703 (30 MIN. two coat) FLAME SPREAD 0 SMOKE DEVELOPED 110
Warranty:
These products are sold on condition that the user will evaluate them to determine their suitability for the user’s intended purpose. Flame Stop, Inc. warrants that each quantity of Flame Stop I will be the kind designated and free of defects. No other warranty is implied, since Flame Stop, Inc., has no control over the application. Additionally,
Resistafire, Inc. cannot provide any additional warranty for products which are sold directly to the consumer for do-it-yourself applications, since we would have no control over the application.
|